Home / Industrial Products / Frequency Converter / FC Series

FC Series

It is the electricity supply system for devices and equipment that require a different frequency from the mains for the operation of the device powered by AC voltage. It is the conversion of the 50Hz mains frequency to the 400Hz or 60Hz frequency required for the operation of the device. Static frequency converters perform the frequency conversion in two stages. First, the input voltage is converted to DC voltage with the help of rectifiers. Then, with the help of the inverter, this DC voltage is converted to AC voltage at the desired frequency. Transistor, thyristor, he says, is used for switching after these processes.

Category Frequency Converter

Input
▪ Voltage (1 Phase) 220VAC±15% Standard (110VAC to 260VAC ±15% available)
▪ Voltage (3 Phase) 3x380VAC±15% Standard (190VAC to 460VAC ±15% available)
▪ Frequency 50, 60 and 400Hz ±10% Standard (other input Hz available)
▪ Phase Rotation Any (Automatic Phase Lock)
▪ Inrush Current 10 x Inom

Output
▪ Power (kVA) 1kVA to 600kVA (Between ranges available)
▪ Frequency 50, 60 and 400Hz ±10% Standard (other input Hz available)
▪ Voltage (1 Phase) 220VAC±15% Standard (110VAC to 260VAC ±15% available)
▪ Voltage (3 Phase) 3x380VAC±15% Standard (190VAC to 460VAC ±15% available)
▪ Voltage Regulation <1% Maximum
▪ Voltage Recovery <50ms @ unbalanced load
▪ Voltage Stability <1% @ balanced load/<3% @ unbalanced load
▪ THDu <2%
▪ Overload Capacity
▪ Continuous @ 110% load
▪ 1 hours @ 125% load
▪ 5 minutes @ 150% load
▪ 20 seconds @ 200% load
▪ Isolation Values 1500, 2000 or 3000VAC input&output/chassis

Physical characteristics
▪ Protection Degree Standard: IP20, (IP21 to IP54 available)
▪ Cooling System Forced Ventilation (Natural cooling, Smart Fans available)
▪ Cable Entry Standard: Bottom (Top, Rear, Side available)
▪ Cabinet Color Standard: RAL7032,7035 (Others available)

Environment
▪ Operating Temperature 0 to 50C°
▪ Storage Temperature-25 to 70C°
▪ Relative Humidity 0 to 100% (non-condensing)
▪ Operating Altitude 1000m from MSL (1% derate each 100m after 1000m)
▪ Acoustic Noise <65dB (depend on capacity)
▪ Isolation Resistance 200MΩ

Communications
▪ Standard Comm. RS232, Dry Contact x4 to x16 (OPT: RS485, TCP and IEC61850)
▪ Paralel Operation 2 Units
▪ HMI Standard: LED/LCD Panel (HMI Touch Panel, Mimic Panel available)

Protections
▪ Protections Overload, Short Circuit, Over Voltage, Under Voltage, Over Temperature
▪ Optional Protections Syncronization Protection, Fan Failure, AC Earth Fault

Standards
▪ IEC 62040 Uninterruptible power systems (UPS) – Part 1&2&3

Main Features: